A Study on SFCL Systems for Korean Power System Application
暂无分享,去创建一个
The recovery time of developing SFCL (superconducting fault current limiter) has an uncertainty. In general, the recovery time is estimated at 1 sec and more, even though the progress of SFCL technology is considered. However, auto-reclosing time of circuit breaker is 0.3 sec in Korean power system. It is impossible to apply only one SFCL to power system because the recovery time is over the reclosing time of protection system. This study proposes two new SFCL systems for power system application. The proposed systems consider auto reclosing action for the protection in practical power system and consist of tow parallel SFCLs
[1] M. Noe,et al. Technical and economical benefits of superconducting fault current limiters in power systems , 1999, IEEE Transactions on Applied Superconductivity.
[2] Jae-Young Yoon,et al. Resistive Hts-Fcl Emtdc Modeling By Using Probabilistic Design Methodology , 2004 .
[3] Mårten Sjöström,et al. Technical and economical impacts on a power system by introducing an HTS FCL , 2001 .
[4] Jae-Young Yoon,et al. Evaluation of the Application Scheme of SFCL in Power Systems , 2004 .