Numerical simulation and analysis of the hot air recirculation phenomenon observed in direct air-cooled system
暂无分享,去创建一个
The hot air recirculation phenomenon observed in direct air- cooled system is numerical simulated and the causes of the hot air recirculation and its influence on air-cooled units are qualitatively analyzed with the help of computational fluid dynamics (CFD) software. The results indicate that the hot air recirculation is a common trouble in the air-cooled power units. It is provoked by the arrangement of the air-cooled island and the environmental condition around the direct air-cooled system, especially the strong wind. The hot air recirculation greatly reduces the heat transfer ability, which will worsen units' vacuum and cause the power units to trip out.
[1] Josua P. Meyer,et al. Simulation of Heat Exchange in Large Air Cooled Condensers , 1998 .
[2] Yan Li,et al. Wind tunnel simulation of exhaust recirculation in an air-cooling system at a large power plant , 2007 .
[3] Detlev G. Kroger,et al. Air-cooled heat exchangers and cooling towers : thermal-flow performance evaluation and design , 2004 .
[4] Hui Li,et al. Wind tunnel simulation on re-circulation of air-cooled condensers of a power plant , 2005 .