Grid connected photovoltaic system with data-based MPPT and fuzzy controlled DVR

This paper presents the impact of a fuzzy logic controlled dynamic voltage restorer on a transformer-less single-stage grid-connected solar photovoltaic system controlled by a data based maximum power point tracking technique. The solar photovoltaic system uses a data based maximum power point technique to derive maximum power from solar photovoltaic array and maintains constant DC voltage by changing modulation index of voltage source converter. A dynamic voltage restorer with pulse width modulated control is introduced to mitigate unbalanced sag in grid voltage and current during fault conditions. Fuzzy logic control (FLC) has been implemented to maintain voltage at grid side for normal as well as for faulted conditions. Simulation results show that distortion in active and reactive power exchange among solar photovoltaic converter, load and grid is reduced during fault conditions. A reduction in total harmonic distortion for all temperature conditions, low and high solar radiation is observed in grid voltage and current. Apart from these, it has been observed that distortion in DC link voltage while deriving maximum power from photovoltaic array is considerably reduced by introducing fuzzy logic controlled dynamic voltage restorer in proposed system.

[1]  Aaas News,et al.  Book Reviews , 1893, Buffalo Medical and Surgical Journal.

[2]  B. Bletterie,et al.  Photovoltaic-inverters as active filters to improve power quality in the grid. What can state-of-the-art equipment achieve? , 2007, 2007 9th International Conference on Electrical Power Quality and Utilisation.

[3]  Narain G. Hingorani,et al.  Introducing custom power , 1995 .

[4]  Akhil Gupta,et al.  THD reduction with reactive power compensation for fuzzy logic DVR based solar PV grid connected system , 2014 .

[5]  B. L. Mathur,et al.  MATLAB Based Modelling and Performance Study of Series Connected SPVA under Partial Shaded Conditions , 2009 .

[6]  Minwon Park,et al.  Power quality control strategy for grid-connected renewable energy sources using PV array and supercapacitor , 2010, 2010 International Conference on Electrical Machines and Systems.

[7]  Akhil Gupta,et al.  Power quality investigation of a solar PV transformer-less grid-connected system fed DVR , 2014 .

[8]  Rahul Dubey,et al.  Analysis of PI and PR controllers for distributed power generation system under unbalanced grid faults , 2011, 2011 International Conference on Power and Energy Systems.

[9]  Pankaj Dahire,et al.  Simulation of D-Statcom and Dvr in Power Systems , 2013 .

[10]  Akhil Gupta,et al.  Power quality improvement of solar photovoltaic transformer-less grid-connected system with maximum power point tracking control , 2014 .

[11]  Hossin Hosseinian,et al.  Power Electronics , 2020, 2020 27th International Conference on Mixed Design of Integrated Circuits and System (MIXDES).

[12]  M. Rezanezhad,et al.  A new control method for Dynamic Voltage Restorer with asymmetrical inverter legs based on fuzzy logic controller , 2010, Simul. Model. Pract. Theory.

[13]  Nadarajah Mithulananthan,et al.  Diode-clamped multi level voltage source converter based medium voltage DVR , 2008 .

[14]  R.K. Varma,et al.  Nighttime Application of PV Solar Farm as STATCOM to Regulate Grid Voltage , 2009, IEEE Transactions on Energy Conversion.

[15]  Chung-Yuen Won,et al.  A tranformerless grid-connected photovoltaic system with active and reactive power control , 2009, 2009 IEEE 6th International Power Electronics and Motion Control Conference.

[16]  Tore Undeland,et al.  Power Electronics: Converters, Applications and Design , 1989 .

[17]  S. Siva Nagaraju SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS , 2007 .