Apparent core losses and core losses in five-limb amorphous transformer of 160 kVA
暂无分享,去创建一个
Significant modifications of the shape of magnetic flux in columns and yokes were observed in the magnetic circuit of four amorphous cores used in a 3-phase transformer. The magnetic losses measured experimentally were significantly higher than the ones calculated theoretically. The values quoted in this paper were obtained in our study, and they are indicative of the need of taking them into consideration when designing 5-limb amorphous distribution transformers.