Effect of voltage sags on adjustable speed drives-a critical evaluation and an approach to improve its performance

In this paper, a critical evaluation of the effect of voltage sags on adjustable speed drives (ASDs) is presented. In particular the DC-link voltage variation under voltage sag and its dependence on source impedance, DC-link inductance and output load is computed. It is shown that for larger source impedance, the DC-link voltage variation under a voltage sag is also large and increases the susceptibility of an ASD and may result in a nuisance trip. The results from the analysis are plotted in per unit quantities and serve as a design guide to assess ASD performance for a variety of sags. In order to improve the performance of ASDs, this paper proposes an integrated boost converter approach. This approach provides ridethrough to critical ASD load during voltage sags without any additional energy storage device. Upon detection of a voltage sag the boost converter operates with suitable duty ratio and maintains the DC-link voltage within acceptable limits. This prevents nuisance tripping and facilitates continuous operation of critical ASD load at rated torque. The proposed integrated boost converter does not introduce any additional semiconductors in the series path of the power flow and is low in cost. A commercially available 480 V, 22 kVA ASD is modified with the integrated boost converter approach and details are discussed. Analysis, simulation and experimental performance of the ridethrough approach are presented.

[1]  T. S. Key,et al.  The electric utility-industrial user partnership in solving power quality problems , 1990 .

[2]  H. G. Sarmiento,et al.  A voltage sag study in an industry with adjustable speed drives , 1994, Proceedings of Industrial and Commercial Power Systems Conference.

[3]  Shashi B. Dewan Optimum Input and Output Filters for a Single-Phase Rectifier Power Supply , 1981, IEEE Transactions on Industry Applications.

[4]  P.A. Crossley,et al.  Characterization of voltage sags in industrial distribution systems , 1997, IAS '97. Conference Record of the 1997 IEEE Industry Applications Conference Thirty-Second IAS Annual Meeting.

[5]  W. W. Carter Control of power quality in modern industry , 1989, IEEE Annual Textile Industry Technical Conference.

[6]  R. Spee,et al.  Voltage sag ride-through for adjustable speed drives with active rectifiers , 1997, IAS '97. Conference Record of the 1997 IEEE Industry Applications Conference Thirty-Second IAS Annual Meeting.

[7]  N. S. Tunaboylu,et al.  Ride-through issues for DC motor drives during voltage sags , 1995, Proceedings IEEE Southeastcon '95. Visualize the Future.

[8]  V.E. Wagner,et al.  Power quality and factory automation , 1988, Conference Record of the 1988 IEEE Industry Applications Society Annual Meeting.

[9]  G. Yalynkaya Characterization of Voltage Sags in Industrial Distribution Systems , 1997 .

[10]  P.N. Enjeti,et al.  A low cost approach to improve the performance of an adjustable speed drive (ASD) under voltage sags and short-term power interruptions , 1998, 6th IEEE Power Electronics Congress. Technical Proceedings. CIEP 98 (Cat. No.98TH8375).

[11]  Math Bollen,et al.  Voltage sags: effects, mitigation and prediction , 1996 .

[12]  C. J. Melhorn,et al.  An evaluation of energy storage techniques for improving ride-through capability for sensitive customers on underground networks , 1996, Proceedings of 1996 IAS Industrial and Commercial Power Systems Technical Conference.