Large-Scale Preventive Security-Constrained Unit Commitment Considering N-k Line Outages and Transmission Losses

This paper presents a new formulation for the preventive security-constrained unit commitment problem modeling N-k line outages and transmission losses. The pre- and post-contingency transmission constraints, representing N-k line outages, are explicitly included by using generalized generation distribution factors. To account for security, a contingency selection procedure based on line outage distribution factors finds a list of worst-case contingencies. Transmission losses are incorporated using piecewise linear expressions. The proposed model is formulated as an instance of mixed-integer linear programming. The effectiveness of the proposed approach is illustrated with the IEEE 57-bus system and the 1,354-bus portion of the European transmission system. As empirically evidenced, the explicit consideration of N-k line outages and transmission losses leads to different decisions in the generation scheduling and dispatch, ensuring secure power system operation.