Impact of different-sized laminar air flow versus no laminar air flow on bacterial counts in the operating room during orthopedic surgery.

BACKGROUND This study investigated the influence of the size of unidirectional ceiling distribution systems on counts of viable microorganisms recovered at defined sites in operating room (ORs) and on instrument tables during orthopedic surgery. METHODS We compared bacterial sedimentation during 80 orthopedic surgeries. A total of 19 surgeries were performed in ORs with a large (518 cm × 380 cm) unidirectional ceiling distribution (colloquially known as laminar air flow [LAF]) ventilation system, 21 procedures in ORs with a small (380 cm × 120 cm) LAF system, and 40 procedures in ORs with no LAF system. Bacterial sedimentation was evaluated using both settle plates and nitrocellulose membranes. RESULTS Multivariate linear regression analysis revealed that the colony-forming unit count on nitrocellulose membranes positioned on the instrument table was significantly associated only with the size of the unidirectional LAF distribution system (P < .001), not with the duration of the surgical intervention (P = .753) or with the number of persons present during the surgical intervention (P = .291). CONCLUSION Our findings indicate that simply having an LAF ventilation system in place will not provide bacteria-free conditions at the surgical site and on the instrument table. In view of the limited number of procedures studied, our findings require confirmation and further investigations on the ideal, but affordable, size of LAF ventilation systems.

[1]  Krinko Anforderungen der Hygiene bei Operationen und anderen invasiven Eingriffen , 2000 .

[2]  O M Lidwell,et al.  Effect of ultraclean air in operating rooms on deep sepsis in the joint after total hip or knee replacement: a randomised study. , 1982, British medical journal.

[3]  P. Lipsett Do we really need laminar flow ventilation in the operating room to prevent surgical site infections? , 2008, Annals of surgery.

[4]  S. Yavuz,et al.  Analysis of Risk Factors for Sternal Surgical Site Infection Emphasizing the Appropriate Ventilation of the Operating Theaters , 2006, Infection Control &#x0026; Hospital Epidemiology.

[5]  J. Charnley,et al.  Postoperative infection in total prosthetic replacement arthroplasty of the hip‐joint with special reference to the bacterial content of the air of the operating room , 1969, The British journal of surgery.

[6]  T. Chow,et al.  Ventilation performance in operating theatres against airborne infection: review of research activities and practical guidance. , 2004, The Journal of hospital infection.

[7]  T. Horan,et al.  Guideline for prevention of surgical site infection. , 2000, Bulletin of the American College of Surgeons.

[8]  J. Charnley,et al.  SECTION II GENERAL ORTHOPAEDICS Postoperative Infection after Total Hip Replacement with Special Reference to Air Contamination in the Operating Room , 1972, Clinical orthopaedics and related research.

[9]  C Pasquarella,et al.  A mobile laminar airflow unit to reduce air bacterial contamination at surgical area in a conventionally ventilated operating theatre. , 2007, The Journal of hospital infection.

[10]  C. Suetens,et al.  Hospitals in Europe Link for Infection Control through Surveillance (HELICS). Inter-country comparison of rates of surgical site infection--opportunities and limitations. , 2007, The Journal of hospital infection.

[11]  Henning Rüden,et al.  Operating Room Ventilation With Laminar Airflow Shows No Protective Effect on the Surgical Site Infection Rate in Orthopedic and Abdominal Surgery , 2008, Annals of surgery.

[12]  A. V. van Griethuysen,et al.  Surveillance of wound infections and a new theatre: unexpected lack of improvement. , 1996, The Journal of hospital infection.

[13]  T. Horan,et al.  Guideline for Prevention of Surgical Site Infection, 1999. Centers for Disease Control and Prevention (CDC) Hospital Infection Control Practices Advisory Committee. , 1999, American journal of infection control.

[14]  L. Cercenelli,et al.  [Cost evaluation of a ventilation system for operating theatre: an ultraclean design versus a conventional one]. , 2004, Annali di igiene : medicina preventiva e di comunita.

[15]  O M Lidwell,et al.  Ultraclean air and antibiotics for prevention of postoperative infection. A multicenter study of 8,052 joint replacement operations. , 1987, Acta orthopaedica Scandinavica.

[16]  C. Glen Mayhall,et al.  Hospital Epidemiology and Infection Control , 2011 .