Dynamic performance of water-based radiant floors during start-up and high-intensity solar radiation

Abstract In this paper, two typical types of radiant floors are examined: concrete core radiant floors and light radiant floors. Their variant dynamic behaviors during intermittent operation are illustrated, and the impact of transient solar radiation is determined through numerical calculation. The concept of the time constant is used to estimate quantitatively the thermal inertia of the different types of radiant floors, especially the response time in the start-up period of the cooling/heating systems. The response time of the concrete core radiant floor is estimated to be 1–3 h, and that of the light floor is estimated to be 10–20 min; these values are consistent with the actual cool-down/heat-up times. When exposed to solar radiation, the cooling capacity of the radiant floors is much higher compared to applications without solar radiation. To estimate the real-time floor surface temperature and cooling capacity with transient solar radiation for both design and operation, a simple calculation method based on thermal capacity of the radiant floor is introduced, and the results accord well with the numerical calculation results. And the dynamic equivalent heat resistance is defined to reflect the thermal behavior of radiant floor with transient solar radiation. In addition, the heat extraction by chilled water in the radiant floor is distinct from the heat absorbed at the floor surface due to the heat storage of the radiant floor, which is also estimated by simple calculation.

[1]  Myoung-Souk Yeo,et al.  Application of the control methods for radiant floor cooling system in residential buildings , 2006 .

[2]  Jianbo Ren,et al.  Very low temperature radiant heating/cooling indoor end system for efficient use of renewable energies , 2010 .

[3]  Zhe Tian,et al.  Establishment and validation of modified star-type RC-network model for concrete core cooling slab , 2011 .

[4]  Yi Jiang,et al.  Application of radiant floor cooling in a large open space building with high-intensity solar radiation , 2013 .

[5]  Bjarne W. Olesen,et al.  Radiant Floor Heating In Theory and Practice , 2002 .

[6]  Doosam Song,et al.  Performance evaluation of a radiant floor cooling system integrated with dehumidified ventilation , 2008 .

[7]  Tim Weber,et al.  An optimized RC-network for thermally activated building components , 2005 .

[8]  Francesco Causone,et al.  Solar radiation and cooling load calculation for radiant systems: Definition and evaluation of the Direct Solar Load , 2010 .

[9]  Celina Filippín,et al.  Transient simulation of a storage floor with a heating/cooling parallel pipe system , 2010 .

[10]  S. Holst,et al.  Using radiant cooled floors to condition large spaces and maintain comfort conditions , 2000 .

[11]  Andreas K. Athienitis,et al.  The effect of solar radiation on dynamic thermal performance of floor heating systems , 2000 .

[12]  경대호,et al.  Radiant Floor Cooling Systems , 2008 .

[13]  Kang Zhao,et al.  Performance of temperature and humidity independent control air-conditioning system in an office bui , 2011 .

[14]  Bjarne W. Olesen,et al.  Low temperature heating and high temperature cooling , 2009 .

[15]  Tao Zhang,et al.  Performance analysis of the air-conditioning system in Xi’an Xianyang International Airport , 2013 .

[16]  Sébastien Thomas,et al.  Model validation of a dynamic embedded water base surface heat emitting system for buildings , 2011 .

[17]  Michele De Carli,et al.  Effect of modelling solar radiation on the cooling performance of radiant floors , 2011 .