An Analysis on Building Energy Load along Core Position, Area Ratio and Orientation
暂无分享,去创建一个
Abstract In this Study, effect of core position, area ratio and orientation of building on energy load is examined using TRNSYS17. This parameters are major parameters of the conceptual design stage. Reference model is square floor plan(1,444m 2 ), centered core and 29% core area ratio. As the results, without considering the building orientation, the annual heating load of central building with 1:1 area ratio is lowest (10.33 kWh/m 2 yr) and the annual cooling load of off-central building with 1:1 area ratio is lowest (59.27 kWh/m 2 yr). As area ratio is bigger, cooling load is lower and heating load is higher. But if we consider building orientation, orders of heating load and cooling load are changed for area ratio and orientation. Key words: Building Energy Load(건물 에너지 부하), Core Position(코어 위치), Area Ratio(종횡비), Orientation(건물 방위) 1. 서 론 1) 최근 온실가스 증가와 기상변화로 인한 에너지 절약에 관한 사회적 요구가 증가하고 있으며, 특히, 건물의 에너지효율화에 대한 관심은 크게 증가하고 있다. 이는 건물부분이 국가 에너지 소비량의 20∼40%를 차지하고 있어 산업 및 수송부분에 비하여 큰 비율을 차지하고 있고, 또한 그 사용비율이 선진국이 될 수록 증가하고 있기 때문