강제 환기에 의한 하절기 복토(覆土) 저장고 결로 방지 대책
暂无分享,去创建一个
In case of earth-covered storage, the condensation occurs on surface of wall and stores in a hot season with high humidity because of low temperature of constructional mass. Therefore, the preventive plans should be considered to protect stores from the damage by corrosion in earth-covered storages. The study was performed at the Magazine of igloo type which is similar to earth-covered storages. A fan was installed at the air outlet for exhaust gas to conduct forced ventilation. The surface and indoor temperature were measured, and then the influence of those on condensation was analyzed. The results of this research are follows; 1) Forced ventilation by a fan affects the rise in surface temperature of walls and stores. 2) The condensation on surface of walls and stores was reduced after operating a fan.