Employing geothermal heat exchanger in natural gas pressure drop station in order to decrease fuel consumption

Natural gas stream must be preheated before pressure reduction takes place at natural gas pressure drop station (CGS). It ensures that the natural gas stream remains above hydrate-formation zone. The heater which is employed to provide the required heat consumes a huge amount of fuel. In this work, the conventional configuration of the natural gas pressure drop station is amended by taking advantage of geothermal energy to provide either all (if applicable) or a considerable portion of the required heat. To evaluate the proposed system in terms of economic and thermal efficiency, Gonbad Kavoos station has been chosen as a case study. Comprehensive thermo-economic analysis has been carried out on the proposed system. The results show that a system comprising 8 boreholes with 150 m depth and 0.15 m diameter each is the most efficient configuration for Gonbad Kavoos station. The achievable providence for the case study was calculated by technical correlations over the standard life time of geothermal systems. Comparison between the proposed system and the previous studied systems proved that the current configuration outperforms all the prior propounded configurations, with IRR (internal rate of return) = 0.155.

[1]  M. Farzaneh-Gord,et al.  Energy and exergy analysis of natural gas pressure reduction points equipped with solar heat and controllable heaters , 2014 .

[2]  Mahmood Farzaneh-Gord,et al.  Energy Destruction in Iran's Natural Gas Pipe Line Network , 2007 .

[3]  Johan Claesson,et al.  An Analytical Method to Calculate Borehole Fluid Temperatures for Time-scales from Minutes to Decades , 2011 .

[4]  Zoi Sagia,et al.  Borehole Resistance and Heat Conduction Around Vertical Ground Heat Exchangers , 2012 .

[5]  R. Mckibbin,et al.  MATHEMATICAL MODELS FOR HEAT AND MASS TRANSPORT IN GEOTHERMAL SYSTEMS , 1998 .

[6]  J. Lund Development and Utilization of Geothermal Resources , 2008 .

[7]  M. Farzaneh-Gord,et al.  Enhancing energy output in Iran's natural gas pressure drop stations by cogeneration , 2008 .

[8]  Saqib Javed,et al.  Thermal modelling and evaluation of borehole heat transfer. , 2012 .

[9]  Mahmood Farzaneh-Gord,et al.  THE SECOND LAW ANALYSIS OF NATURAL GAS BEHAVIOUR WITHIN A VORTEX TUBE , 2013 .

[10]  M. H. Najafimoud,et al.  INVESTIGATION OF RELATIONSHIP BETWEEN AIR AND SOIL TEMPERATURE AT DIFFERENT DEPTHS AND ESTIMATION OF THE FREEZING DEPTH (CASE STUDY: KHORASAN RAZAVI) , 2008 .

[11]  Mahmood Farzaneh-Gord,et al.  Feasibility of accompanying uncontrolled linear heater with solar system in natural gas pressure drop stations , 2012 .

[12]  Alireza Bahadori,et al.  A review of geothermal energy resources in Australia: Current status and prospects , 2013 .

[13]  Emanuele Borgonovo,et al.  A note on the sensitivity analysis of the internal rate of return , 2012 .

[14]  Michaël Kummert,et al.  Simulation Of Ground-coupled Heat Pump Systems Using A Spectral Approach , 2013, Building Simulation Conference Proceedings.

[15]  H. R. Rahbari,et al.  Feasibility of employing solar energy in natural gas pressure drop stations , 2011 .

[16]  Frank P. Incropera,et al.  Fundamentals of Heat and Mass Transfer , 1981 .