Performance Assessment of 35 Cold Hydrodynamic Compressors for the 1.8 K Refrigeration Units of the LHC
暂无分享,去创建一个
The cooling capacity below 2 K for the superconducting magnets in the Large Hadron Collider (LHC) at CERN will be provided by eight refrigeration units of 2400 W at 1.8 K, each of them coupled to one 18 kW at 4.5 K refrigerator. The supply of the series units was linked to successful testing and acceptance of the pre‐series units delivered by the two selected vendors. The two pre‐series units were temporarily installed in a dedicated test station to validate the overall capacity and to properly assess the performance of specific components such as the cold compressors. The cold‐compressor cartridges to be installed in the following six series, and the associated spare cartridges, were intensively and systematically tested in the test station. After a brief description of the test bench and the main achieved features of the pre‐series units, we will present the results of the tests of 35 cold‐compressor cartridges. These tests show isentropic efficiency in the 75 % range, with excellent reproducibility and...