Thermal considerations in specifying dry type transformers

Thermal tests under different loading conditions are performed on a prototype 2500 kVA ventilated dry type transformer and six full size test coils with imbedded thermocouples in the windings. The test data indicated that the hottest spot temperature allowance used in IEEE and IEC standards is too low for ventilated dry type transformers above 500 kVA. It is impossible to design ventilated dry type transformers above 500 kVA with an average temperature rise of 150 degrees C without exceeding the permissible hottest spot temperature rise of 180 degrees C due to large thermal gradients. The average temperature rise for ventilated dry type transformers above 500 kVA with 220 degrees C insulation temperature class should be 120 degrees C. IEEE standards should require measurement of hottest spot temperature rise on prototype transformers or windings as a design test to qualify a design family and the manufacturer's mathematical models. The specification suggested should be used until IEEE standards are revised.<<ETX>>

[1]  A. A. Halacsy,et al.  Temperature Rise of Dry-Type Transformers , 1958, Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems.

[2]  Chas. F. Scott,et al.  Early history of the A-C system in America , 1936, Electrical Engineering.

[3]  L. W. Pierce An investigation of the temperature distribution in cast-resin transformer windings , 1991 .

[4]  L. W. Pierce Hottest spot temperatures in ventilated dry type transformers , 1994 .

[5]  A. A. Halacsy,et al.  Transformer invented 75 years ago , 1961, Electrical Engineering.

[6]  J. Frank,et al.  Specifying dry-type distribution transformers for solid state applications , 1988, Conference Record, Industrial and Commercial Power Systems Technical Conference, 1988..

[7]  W. W. Satterlee Design and operating characteristics of modern dry-type air-cooled transformers , 1944, Electrical Engineering.

[8]  L. W. Pierce Predicting hottest spot temperatures in ventilated dry type transformer windings , 1994 .

[9]  Melvin L. Manning The Application of Class-H Insulation to Transformers , 1951, Transactions of the American Institute of Electrical Engineers.

[10]  L. C. Whitman Loading of Ventilated Dry-Type Transformers , 1957, Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems.

[11]  L. C. Whitman,et al.  Hot-Spot Temperatures in Dry-Type Transformer Windings , 1944, Transactions of the American Institute of Electrical Engineers.

[12]  L. C. Whitman Co-ordination of Dry-Type Transformer Models with Transformer Geometry [includes discussion] , 1956, Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems.

[13]  E. W. Rice The Relative Fire-Risk of Oil and Air-Blast Transformers , 1904, Transactions of the American Institute of Electrical Engineers.

[14]  W. L. R. Emmet Existing Commercial Applications of Electrical Power from Niagara Falls , 1895, Transactions of the American Institute of Electrical Engineers.