GPS travelling wave fault locator systems: investigation into the anomalous measurements related to lightning strikes

A new fault location system based on the travelling wave principle and capable of locating faults on power lines to within /spl plusmn/one tower span (300 m) has been successfully developed and applied to BC Hydro's extensive 500 kV network. Unlike earlier schemes which are based on impedance measurements, its accuracy is not affected by load conditions, high grounding resistance and most notably series capacitor banks. This system measures the time of arrival of a fault-generated travelling wave at the line terminals using the precise timing signals from the Global Positioning System (GPS). Operating experience with the fault locator on lightning related faults indicated highly accurate results were obtained for the majority of the cases. In a few of the lightning-caused disturbances, the system gave anomalous measurements. This paper describes the operation of the system, summarizes the operating experience and explains the observed anomalous measurements.

[1]  M. Ianoz,et al.  Comparison of two coupling models for lightning-induced overvoltage calculations , 1995 .

[2]  K. Berger,et al.  Novel observations on lightning discharges: Results of research on Mount San Salvatore , 1967 .

[3]  A. M. Mousa,et al.  Effect of shielding by trees on the frequency of lightning strokes to power lines , 1988 .

[4]  P. Chowdhuri Response of overhead lines of finite length to nearby lightning strokes , 1991 .

[5]  W. W. Lewis,et al.  Lightning Investigation on Transmission Lines , 1930, Transactions of the American Institute of Electrical Engineers.

[6]  A. Eriksson,et al.  Lightning-Induced Overvoltages on Overhead Distribution Lines , 1982 .

[7]  P. F. Gale The use of GPS for precise time tagging of power system disturbances and in overhead line fault location , 1994 .

[8]  K. B. McEachron,et al.  Lightning to the Empire State Building , 1939, Transactions of the American Institute of Electrical Engineers.

[9]  A. M. Mousa,et al.  The lightning performance of unshielded steel-structure transmission lines , 1989 .

[10]  A. T. Johns,et al.  A new travelling-wave based scheme for fault detection on overhead power distribution feeders , 1992 .

[11]  A. M. Mousa,et al.  The distribution of lightning strokes to towers and along the span of shielded and unshielded power lines , 1990, Canadian Journal of Electrical and Computer Engineering.

[12]  Herbert Songster,et al.  The East Coast Lightning Detection Network , 1986, IEEE Power Engineering Review.

[13]  J. M. Clayton,et al.  Application of Arresters for Complete Lightning Protection of Substations , 1958, Transactions of the American Institute of Electrical Engineers Part III Power Apparatus and Systems.