Relay protection coordination integrated optimal placement and sizing of distributed generation sources in distribution networks

Summary form only given. The integration of distributed generation (DG) sources can cause significant impacts on distribution networks, particularly the changes in magnitudes and directions of short circuit currents that may lead to false tripping or fail to trip over-current protection relays in the system. It is expensive and technically challenging to redesign/reconfigure and/or to replace the original protection system for a distribution network. If not appropriately handled, this issue can be a big hurdle before the wide use of DG. Based on the impact analysis of the number of DGs, their locations and capacities upon short circuit currents, this paper presents an optimal DG placement method to maximize the penetration level of DG in distribution networks without changing the original relay protection schemes. Genetic algorithm (GA) is used to find the optimal locations and sizes of DG in distribution networks. Simulation studies have been carried out on a three-feeder test distribution network and a widely used 33-node test system to show the effectiveness of the proposed method.