Estimation of Thermal Balance in Heptane Pool Fire
暂无分享,去创建一个
In order to predict the scale dependency of fire property in oil tank fires, we estimated the thermal balance of generated heat from the fire with a simple fire model, a so-called one mesh model. In this estimation, both ex perimental values of burning rate and air entrainment in heptane pool fires were used. For 1 m tank fires, it was found that about 70% of the generated heat was lost as upward convective heat and about 30% was lost as radiative heat, and only about 1% was used for fuel vaporization. The ratio of upward convec tive heat became larger with tank size. Experimental results show that the radiative fraction went down in fires larger than 1 m diameter because of the huge smoke emission.
[1] M. Pinar Mengüç,et al. Thermal Radiation Heat Transfer , 2020 .
[2] M. Sibulkin. Estimates of the Effect of Flame Size on Radiation from Fires , 1973 .
[3] H. C. Hottel,et al. Radiant heat exchange in a gas-filled enclosure: Allowance for nonuniformity of gas temperature , 1958 .
[4] Koseki Hiroshi,et al. Air entrainment and thermal radiation from heptane pool fires , 1988 .