Pool Boiling of FC-72 and HFE-7100

This work reported the boiling characteristics of FC-72 and HFE-7100 at atmospheric pressure and at a liquid subcooling of 0-20 K. The FC-72 exhibits a more efficient nucleate boiling mode and a higher critical heat flux (CHF) than the HFE-7100. For film boiling mode, HFE-7100 becomes more efficient.