Energy influence of the IHX with R22 drop-in and long-term substitutes in refrigeration plants

Abstract This work focuses on the investigation of new drop-in or long-term refrigerants for low evaporating temperatures that can be used as substitutes for HCFC-22, which is gradually being phased-out. This process is already in progress in European countries (Regulation CE-1005/2009) and has been accelerated in Article 5 Countries of the Montreal Protocol. Specifically, in this work the energy influence of the suction line/liquid line heat exchanger on the new substitute fluids is addressed from an experimental approach. The study has been based on experimental measurements in a single-stage vapour compression refrigeration plant, which has been tested in the same external conditions operating with and without an Internal Heat Exchanger (IHX). The energy influence of the IHX working with R22 and three potential substitutes for low temperature applications, the chlorine-free drop-in fluids R417B and R422A and the chlorine-free long-term substitute R404A has been analysed. From the experimental results, reductions in capacity and COP have been observed when R22 is replaced by the drop-in fluids, although the presence of an IHX can help to lessen these reductions. Furthermore, the criteria that are usually employed to determine the energy advantage or disadvantage of the use of the IHX with the new refrigerants have been tested, the results confirming that they remain valid for them.

[1]  Ramón Cabello,et al.  On-site study of HCFC-22 substitution for HFC non-azeotropic blends (R417A, R422D) on a water chiller of a centralized HVAC system , 2010 .

[2]  Ramón Cabello,et al.  Experimental evaluation of HCFC-22 replacement by the drop-in fluids HFC-422A and HFC-417B for low temperature refrigeration applications , 2011 .

[3]  Rita Mastrullo,et al.  An analysis of the performances of a vapour compression plant working both as a water chiller and a heat pump using R22 and R417A , 2004 .

[4]  Alfonso William Mauro,et al.  Experiments during flow boiling of a R22 drop-in: R422D adiabatic pressure gradients , 2009 .

[5]  S. Klein,et al.  Refrigeration System Performance using Liquid-Suction Heat Exchangers , 2000 .

[6]  Joaquín Navarro-Esbrí,et al.  Experimental evaluation of the internal heat exchanger influence on a vapour compression plant energy efficiency working with R22, R134a and R407C , 2005 .

[7]  Ciro Aprea,et al.  A criterion for predicting the possible advantage of adopting a suction/liquid heat exchanger in refrigerating system , 1999 .

[8]  Rodrigo Llopis,et al.  Energetic evaluation of an internal heat exchanger in a CO2 transcritical refrigeration plant using experimental data , 2011 .

[9]  R. Llopis,et al.  HCFC-22 replacement with drop-in and retrofit HFC refrigerants in a two-stage refrigeration plant for low temperature , 2012 .

[10]  Piotr A. Domanski,et al.  Theoretical Evaluation of the Vapor Compression Cycle With a Liquid-Line/Suction-Line Heat Exchanger, Economizer, and Ejector (NISTIR 5606) , 1995 .

[11]  W. B. Gosney Principles of Refrigeration , 1982 .

[12]  K. C. Mendonça,et al.  Experimental Study on Lateral Capillary Tube-Suction Line Heat Exchangers , 1998 .

[13]  J. Fernández-Seara,et al.  Vapour condensation of R22 retrofit substitutes R417A, R422A and R422D on CuNi turbo C tubes , 2010 .

[14]  C. Bullard,et al.  Diabatic flow instabilities in capillary tube-suction line heat exchangers , 2000 .

[15]  P. Domanski,et al.  Evaluation of suction-line/liquid-line heat exchange in the refrigeration cycle , 1994 .