이더넷 통신기반의 자율적 고장 판단 및 복구 방법론 연구

This paper proposes an autonomous fault determination. fault zone isolation and fault restoration strategy based on the ethernet communication as a new attempt to solve the problem the of the existing central control method. In proposed method, The FRTU(Feeder Remote Terminal Unit)s on the feeder determines autonomously where the faulted zone is by exchanging the voltage and current information with neighbor FRTUs based on the network communication, and then separates the faulted zone in an nil-voltage status to make the protective device to reclose successively. In particular, the minimization of outage time and relational load balancing is archived by each interconnection switch which determines autonomously the load zone to be allocated among those zones after the sound outage zones was separated individually. Finally, to show effectiveness of the proposed fault restoration strategy, the several fault cases are simulated for the test distribution system, and the load balancing index of the proposed solution is compared with all of feasible solutions.