Full-scale evaluation of halon replacement agents
暂无分享,去创建一个
Full-scale fire suppression testing of HFC-227ea and HCFC Blend A was conducted in a 121 m3 compartment. HFC-227ea was tested at 7.6 and 8.8%; HCFC Blend A was tested at 8.6, 9.3, 10, 12 and 14% (by volume). Information on discharge characteristics and fire suppression performance of these halon replacement agents was obtained. HFC-227ea extinguished all test fires at the test concentrations. HCFC Blend A extin guished all test fires only at test concentrations of 12% or higher. These two agents produced halogenated acid gases whose quantity depended on the type, concentration and discharge of the agents and the size of the test fires. Language: en
[1] Andrew K. Kim,et al. FTIR spectroscopic measurement of halogenated compounds produced during fire suppression tests of two halon replacements , 1998 .
[2] Joseph Z. Su,et al. Production Of Carbon Monoxide During Fire Suppression Using Halon Replacements , 2000 .
[3] N. Irving Sax,et al. Dangerous properties of industrial materials , 1957 .