Managing Water Quality in Premise Plumbing: Subject Matter Experts’ Perspectives and a Systematic Review of Guidance Documents

Although many guidance documents have been developed to inform the design and operation of building water systems to ensure safe water quality, there is a lack of consensus on some topics. This study interviewed 22 subject matter experts (SMEs) to identify topics of concern for managing water quality in buildings and compared SME views with information available on these topics in 15 systematically screened important guidance documents. The study found 18 design and 11 operational topics as critical for managing water quality in buildings. No one guidance document addressed all these topics, suggesting that a compendium of available guidance is needed. SMEs most frequently recommended temperature and residual disinfectant measurements as good parameters for monitoring overall building water quality. Both SME and guidance document recommendations for temperature for controlling opportunistic pathogen growth were reasonably consistent with water heater setpoint >60 °C. However, hot water temperature recommendations varied between 50 and 55 °C for other locations (i.e., the water temperature at the tap or end of the return loop). On the contrary, recommendations for disinfectant residual levels (0.2–2.0 mg/L), flushing frequency (1–14 days), and allowable time for hot water to reach the tap (10–60 s) were not consistent. While this study was able to reconcile diverging views on some of the water quality topics, such as identifying common guidance for water heater set point to at least 60 °C, it also highlights lack of definitive guidance on other critical topics, such as residual level, flushing frequency, hot water time to tap, and the use of thermostatic mixing valves, indicating that these are significant knowledge gaps that need further investigation. The study concludes that there is a need for developing evidence-based guidance, particularly on the topics where expert opinions diverged.

[1]  Amy Pruden,et al.  Water heater temperature set point and water use patterns influence Legionella pneumophila and associated microorganisms at the tap , 2015, Microbiome.

[2]  R. Berkelman,et al.  Legionellosis on the Rise: A Review of Guidelines for Prevention in the United States , 2015, Journal of public health management and practice : JPHMP.

[3]  M. Beach,et al.  Direct healthcare costs of selected diseases primarily or partially transmitted by water , 2012, Epidemiology and Infection.

[4]  R. Berkelman,et al.  A Review of Guidelines for the Primary Prevention of Legionellosis in Long-Term Care Facilities. , 2015, Journal of the American Medical Directors Association.

[5]  Marco Propato,et al.  Vulnerability of water distribution systems to pathogen intrusion: how effective is a disinfectant residual? , 2004, Environmental science & technology.

[6]  L. Cooley,et al.  Waterborne Disease Outbreaks Associated With Environmental and Undetermined Exposures to Water — United States, 2013–2014 , 2017, MMWR. Morbidity and mortality weekly report.

[7]  J. Gargano,et al.  Outbreaks Associated With Environmental and Undetermined Water Exposures — United States, 2011–2012 , 2015, MMWR. Morbidity and mortality weekly report.

[8]  P. A. West,et al.  Occupational Risks from Infectious Diseases in the Water Industry , 1990 .

[9]  Michèle Prévost,et al.  Temperature diagnostic to identify high risk areas and optimize Legionella pneumophila surveillance in hot water distribution systems. , 2015, Water research.

[10]  P. Biernacki,et al.  Snowball Sampling: Problems and Techniques of Chain Referral Sampling , 1981 .