Potential Operation and Maintenance (O&M) Savings in the Clinical Science Building at UTMB
暂无分享,去创建一个
An optimized HVAC operation schedule has been developed using the simplified
model analysis with the LoanSTAR measured hourly data and the EMCS measured
operation parameters at UTMB. An annual savings of $73,700 can be realized by
implementing this optimized schedule by changing the EMCS control program. The
majority of the energy savings are due to the reduction in chilled water consumption and
the substantial reduction of reheat. Our analysis indicates that the indoor comfort level
will not be degraded by this measure. It can reduce the building's current annual energy
costs by $73,700 or 21%.
This report discusses a simplified model analysis and the methodology of
identifying one type of O&M improvement and summarizes the potential savings from this
measure.