인접한 고층건물의 豊荷重 상호간섭에 관한 연구

Wind load is evaluated based on Standard Design Loads for Building of AIK(Architectural Institute of Korea), which was obtained from wind-tunnel experiment for an isolated building in open country, actual wind load can be different from the code because of terrain, building geometry, wind direction, separation distance between the buildings. Among them. separation distance is the most important factor. This paper presents the interference factor for sqaue section high-rise building structure, focusing on the separation distance. Interference factor was obtain from the force balance test in a wind tunnel.