Impact of LVRT capability of wind turbines on distance protection of AC grids

When a transmission line close to a wind farm (WF) with doubly fed induction generators (DFIGs) experiences a short circuit (SC) fault, the resulting voltage dip on the WF terminal bus may trigger actions from the crowbar circuits of DFIGs. These actions prevent high rotor currents that can be damaging to power electronic converters. Under this condition, DFIGs have to absorb reactive power from the external power grid to provide generator excitation. As a result, it will further depress the voltage at the WF terminal bus and affect the protective relay operation of transmission lines in severe situations. This paper is concerned with the performance of distance relays on a power grid with WFs that are equipped with crowbar circuits. Numerical simulations are conducted on IEEE 39 bus system with WF connections. It is found that the fault on the terminal line of a WF is likely to induce mis-coordination of distance relays, leading to system security problems.

[1]  Nicholas Jenkins,et al.  Comparison of fixed speed and doubly-fed induction wind turbines during power system disturbances , 2003 .

[2]  Li Ran,et al.  Control of a doubly fed induction generator in a wind turbine during grid fault ride-through , 2006, IEEE Transactions on Energy Conversion.

[3]  Peter Tavner,et al.  Control of a doubly fed induction generator in a wind turbine during grid fault ride-through , 2006 .

[4]  T.S. Sidhu,et al.  Performance of distance relays on shunt-FACTS compensated transmission lines , 2005, IEEE Transactions on Power Delivery.

[5]  Chen-Ching Liu,et al.  Tripping of wind turbines during a system fault , 2008, 2008 IEEE Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century.

[6]  Chen-Ching Liu,et al.  Economic and technical criteria for designing future off-shore HVDC grids , 2010, 2010 IEEE PES Innovative Smart Grid Technologies Conference Europe (ISGT Europe).

[7]  Ganapati Panda,et al.  Adaptive relay setting for flexible AC transmission systems (FACTS) , 2000, 2000 IEEE Power Engineering Society Winter Meeting. Conference Proceedings (Cat. No.00CH37077).

[8]  G Pannell,et al.  Minimum-Threshold Crowbar for a Fault-Ride-Through Grid-Code-Compliant DFIG Wind Turbine , 2010, IEEE Transactions on Energy Conversion.

[9]  G. Joos,et al.  Adaptive Distance Relay Setting for Lines Connecting Wind Farms , 2007, IEEE Transactions on Energy Conversion.

[10]  J. Morren,et al.  Ridethrough of wind turbines with doubly-fed induction generator during a voltage dip , 2005, IEEE Transactions on Energy Conversion.

[11]  R.K. Aggarwal,et al.  Performance evaluation of a distance relay as applied to a transmission system with UPFC , 2006, IEEE Transactions on Power Delivery.

[12]  Luis Marroyo,et al.  Ride Through of Wind Turbines With Doubly Fed Induction Generator Under Symmetrical Voltage Dips , 2009, IEEE Transactions on Industrial Electronics.