Prototype evaluation of over 10W/cm3 high power density converter for 400V-DC power distribution system in data center

This paper presents the high power density and high efficiency DC-DC converter for 400V-DC power distribution system. The full-bridge converter is used for typical topology. However, there are some problems such as surge voltage occurrence. Here, the miniaturization of isolated DC-DC converter using the LLC resonant converter which can achieve soft-switching operation without auxiliary circuit is considered. The prototype test circuit is evaluated by experimentally. As a result, the high power density of 12.5W/cm3 and high efficiency of over 95% is achieved.

[1]  Keiichi Hirose,et al.  Development of 400 Vdc power distribution system and 400 Vdc output rectifier , 2009, INTELEC 2009 - 31st International Telecommunications Energy Conference.

[2]  K. Morita Novel ultra low-noise soft switch-mode power supply , 1998, INTELEC - Twentieth International Telecommunications Energy Conference (Cat. No.98CH36263).

[3]  K. Hirose,et al.  Study on Field Demonstration of Multiple Power Quality Levels System in Sendai , 2006, INTELEC 06 - Twenty-Eighth International Telecommunications Energy Conference.

[4]  A. Pratt,et al.  Evaluation of 400V DC distribution in telco and data centers to improve energy efficiency , 2007, INTELEC 07 - 29th International Telecommunications Energy Conference.

[5]  F. Lee,et al.  LLC resonant converter for front end DC/DC conversion , 2002, APEC. Seventeenth Annual IEEE Applied Power Electronics Conference and Exposition (Cat. No.02CH37335).

[6]  A. Sannino,et al.  Feasibility of a DC network for commercial facilities , 2002, Conference Record of the 2002 IEEE Industry Applications Conference. 37th IAS Annual Meeting (Cat. No.02CH37344).

[7]  Toshifumi Ise,et al.  A Configuration and Control Method of DC Loop Type Distribution System Including Distributed Generators , 2003 .

[8]  R. D. De Doncker,et al.  Calculation of losses in ferro- and ferrimagnetic materials based on the modified Steinmetz equation , 1999, Conference Record of the 1999 IEEE Industry Applications Conference. Thirty-Forth IAS Annual Meeting (Cat. No.99CH36370).

[9]  T. Tanaka,et al.  Guidelines for power-supply systems for datacom equipment in NTT , 2002, 24th Annual International Telecommunications Energy Conference.

[10]  Yanjun Zhang,et al.  1MHz-1kW LLC Resonant Converter with Integrated Magnetics , 2007, APEC 07 - Twenty-Second Annual IEEE Applied Power Electronics Conference and Exposition.

[11]  J.W. Kolar,et al.  Design of a 5kW, 1U, 10kW/ltr. resonant DC-DC converter for telecom applications , 2007, INTELEC 07 - 29th International Telecommunications Energy Conference.

[12]  R. Petkov,et al.  Optimum design of a high-power, high-frequency transformer , 1996 .

[13]  H. Ikebe Power systems for telecommunications in the IT age , 2003, The 25th International Telecommunications Energy Conference, 2003. INTELEC '03..

[14]  C. Foster,et al.  High voltage DC power distribution for telecommunications facilities , 2008, INTELEC 2008 - 2008 IEEE 30th International Telecommunications Energy Conference.