Continuous on-line partial discharge monitoring of generator stator windings
暂无分享,去创建一个
The use of on-line partial discharge (PD) measurements as an indicator of stator winding insulation condition, is well known. Trending results from on-line PD measurements over time, often allows maintenance personnel to become aware of developing stator insulation problems in motors and generators, and take corrective measures before failure occurs. However, partial discharge measurements on operating rotating machines can be influenced by conditions such as humidity, temperature, terminal voltage, and load. Thus, to provide reliable data which can be trended, it is important to take readings under similar machine operating conditions. In remote plants, or on pump storage units which are frequently cycled, it can be both time consuming and costly to ensure that personnel are available to take PD readings under ideal conditions occur. This paper describes the development of an automatic partial discharge monitoring system which is permanently connected to relevant machine sensors and can be configured to collect PD data when suitable conditions are met. The operating principles of the system are described, and some results are presented from data collected to date on 30 hydrogenerators.
[1] J. S. Johnson,et al. Detection of Slot Discharges in High-Voltage Stator Windings During Operation , 1951, Transactions of the American Institute of Electrical Engineers.
[2] W. McDermid,et al. Practical online partial discharge tests for turbine generators and motors , 1994, IEEE Power Engineering Review.