Thermal performance prediction and analysis on the economized vapor injection air-source heat pump in cold climate region of China

Abstract The air-source heat pump with an economized vapor injection technique has the distinct advantages of performance and stability for space heating and hot water supply in cold area. However, it is unreasonable to evaluate and predict the thermal performance by the nominal working conditions in different areas and environmental conditions. The experimental set up of economized vapor injection air-source heat pump (EVI-ASHP) system was established in cold region of China. The experimental results showed that the air-source heat pump with the EVI technique could improve thermal performance 4–6% than that without EVI. The relationship of COP and condenser inlet and ambient temperature difference was linearly dependent in the same environmental relative humidity. In order to obtain the empirical equations of COP, the linear and negative exponential corrections of the temperature difference of ambient dry-bulb and wet bulb were used when the electromagnetic valve is on or off, respectively. The monthly and hourly thermal performance of four cities in cold and severe cold region in China was compared and analyzed in the climatic condition of the typical meteorological year.

[1]  José M. Corberán,et al.  Analysis and optimization of subcritical two-stage vapor injection heat pump systems , 2014 .

[2]  Reinhard Radermacher,et al.  Two-stage heat pump system with vapor-injected scroll compressor using R410A as a refrigerant , 2009 .

[3]  Yongchan Kim,et al.  Performance comparison between R410A and R32 multi-heat pumps with a sub-cooler vapor injection in the heating and cooling modes , 2016 .

[4]  Yang Yao,et al.  Experimental study on performance of a solar-air source heat pump system in severe external conditions and switchover of different functions , 2016 .

[5]  Jianlin Yu,et al.  Performance analysis of a new ejector enhanced vapor injection heat pump cycle , 2015 .

[6]  Rodrigo Llopis,et al.  Experimental analysis of energy performance of modified single-stage CO2 transcritical vapour compression cycles based on vapour injection in the suction line , 2012 .

[7]  B. Tao,et al.  Experimental investigation on vapor injection heat pump with a newly designed twin rotary variable speed compressor for cold regions , 2016 .

[8]  S. J. Kline,et al.  Describing Uncertainties in Single-Sample Experiments , 1953 .

[9]  Masud Behnia,et al.  Seasonal Performance Rating of Heat Pump Water Heaters , 2004 .

[10]  Jianlin Yu,et al.  Performance analysis of a novel dual-nozzle ejector enhanced cycle for solar assisted air-source heat pump systems , 2014 .

[11]  Jaehyeok Heo,et al.  Effects of vapor injection techniques on the heating performance of a CO2 heat pump at low ambient temperatures , 2014 .

[12]  Ma Guoyuan,et al.  Research on air-source heat pump coupled with economized vapor injection scroll compressor and ejector , 2011 .

[13]  N. Hewitt,et al.  The experimental analysis of the effect of ambient factors on the defrosting of economised vapour injection compressor air source heat pump in marine climates , 2013 .

[14]  Mitsuhiro Fukuta,et al.  An investigation of the performance of a scroll compressor under liquid refrigerant injection , 2001 .

[15]  Ali Hakkaki-Fard,et al.  Improving cold climate air-source heat pump performance with refrigerant mixtures☆ , 2015 .

[16]  Shiming Deng,et al.  A study on the performance of the airside heat exchanger under frosting in an air source heat pump water heater/chiller unit , 2004 .

[17]  Guangcai Gong,et al.  Research on frost formation in air source heat pump at cold-moist conditions in central-south China , 2013 .