Abstract Voltage sags are among the most important power quality events due to their economic effect on all types of customers, especially industrial users. Normal contactors would open when a voltage sag of given depth, duration, phase-jump, and starting angle takes place. Results given here were obtained from a series of experimental tests carried out on six contactors with dissimilar characteristics and manufacturers. The traditional immunity curves (or time/voltage characteristics) were obtained. The tested contactors show similar behavior, with very small variations. A few tests were conducted to analyze the increase in contact voltage drop due to voltage sag presence in order to investigate the contacts welding under rated-current conditions.