Experiments on the characteristics of evaporation of R410A in brazed plate heat exchangers with different geometric configurations

Abstract Experiments on the evaporative heat transfer and pressure drop in the brazed plate heat exchangers were performed with refrigerants R410A and R22. The plate heat exchangers with different 45°, 35°, and 20° chevron angles are used. Varying the mass flux of refrigerant (13–34 kg/m2 s), the evaporating temperature (5, 10 and 15 °C), the vapor quality (0.9–0.15) and heat flux (2.5, 5.5 and 8.5 kW/m2), the evaporation heat transfer coefficients and pressure drops were measured. The heat transfer coefficient increases with increasing vapor quality and decreasing evaporating temperature at a given mass flux in all plate heat exchangers. The pressure drop increases with increasing mass flux and quality and with decreasing evaporating temperature and chevron angle. It is found that the heat transfer coefficients of R410A are larger than those of R22 and the pressure drops of R410A are less than those of R22. The empirical correlations of Nusselt number and friction factor are suggested for the tested PHEs. The deviations between correlations and experimental data are within ±25% for Nusselt number and ±15% for friction factor.

[1]  Davide Del Col,et al.  Experimental investigation on condensation heat transfer and pressure drop of new HFC refrigerants (R134a, R125, R32, R410A, R236ea) in a horizontal smooth tube , 2001 .

[2]  R. Yun,et al.  A generalized correlation for evaporation heat transfer of refrigerants in micro-fin tubes , 2002 .

[3]  S. Kandlikar A General Correlation for Saturated Two-Phase Flow Boiling Heat Transfer Inside Horizontal and Vertical Tubes , 1990 .

[4]  P. Argyropoulos,et al.  Air–water two-phase flow and heat transfer in a plate heat exchanger , 2002 .

[5]  Akio Miyara,et al.  Condensation heat transfer and flow pattern inside a herringbone-type micro-fin tube , 2000 .

[6]  W. Focke,et al.  Flow visualization in parallel-plate ducts with corrugated walls , 1986, Journal of Fluid Mechanics.

[7]  M. Kedzierski Effect of Inclination on the Performance of a Compact Brazed Plate Condenser and Evaporator , 1995 .

[8]  M. Goto,et al.  Condensation and evaporation heat transfer of R410A inside internally grooved horizontal tubes , 2001 .

[9]  R. Moffat Using Uncertainty Analysis in the Planning of an Experiment , 1985 .

[10]  Tsing-Fa Lin,et al.  Saturated flow boiling heat transfer and pressure drop of refrigerant R-410A in a vertical plate heat exchanger , 2002 .

[11]  Steven J. Eckels,et al.  Local Heat Transfer Coefficients during Condensation of R-22 and R-32/R-125 Mixtures , 1999 .

[12]  Tsing-Fa Lin,et al.  Evaporation Heat Transfer and Pressure Drop of Refrigerant R-134a in a Plate Heat Exchanger , 1999 .

[13]  Y. Y. Hsieh,et al.  Subcooled flow boiling heat transfer of R-134a and the associated bubble characteristics in a vertical plate heat exchanger , 2002 .