An important aspect of the design of data centers involves sizing of the perforated floor tiles for return of cold air, the size of the space under the raised floor, and placement of the DP equipment and modular chillers. The flow through individual perforated tiles needs to fulfil the cooling requirements of the computer equipment placed adjacent to them. The novelty of this paper lies in the treatment of the volume under the raised floor as a uniformly pressurized plenum. The accuracy of the Pressurized Plenum model is demonstrated with reference to a computational fluid dynamics (CFD) analysis of the recirculating flow under the raised floor and the limits of its validity are also identified. The simple model of the volume under the raised floor enables use of the technique of flow network modeling (FNM) for the prediction of the distribution of flow rates exiting from the various tiles. An inverse design method is proposed for one-step design of the perforated tiles and flow balancing plates for individual chillers. Subsequent use of the FNM technique enables assessment of the performance of the actual system. Further, required design changes to an existing system can also be evaluated using the FNM analysis in a simple, quick, and accurate manner. The resulting design approach is very simple and efficient, and is well suited for the design of modern data centers.
[1]
P. Cinato,et al.
An innovative approach to the environmental system design for TLC rooms in Telecom Italia
,
1998,
INTELEC - Twentieth International Telecommunications Energy Conference (Cat. No.98CH36263).
[2]
C. E. Bullock,et al.
The Sistine Chapel : HVAC design for special-use buildings
,
1996
.
[3]
Guohui Gan,et al.
Predicting air flow and thermal comfort in offices
,
1994
.
[4]
S. Patankar.
Numerical Heat Transfer and Fluid Flow
,
2018,
Lecture Notes in Mechanical Engineering.
[5]
O. G. Martynenko,et al.
Handbook of hydraulic resistance
,
1986
.