Spectral domain arcing fault recognition and fault distance calculation in transmission systems
暂无分享,去创建一个
A new numerical algorithm for recognizing arcing faults for the purpose of automatic reclosing is presented. The fault distance can also be calculated using this algorithm. The solution for both symmetrical and unsymmetrical faults is given. A simple empirical arc voltage model is obtained through a table of numerical values. By means of computer simulation and laboratory testing it is shown that the algorithm can be used as an effective tool in transmission and distribution system protection.
[1] A. T. Johns,et al. Neural-network based adaptive single-pole autoreclosure technique for EHV transmission systems , 1994 .
[2] Vladimir Terzija,et al. A new approach to the arcing faults detection for fast autoreclosure in transmission systems , 1995 .
[3] Yuan Xiao,et al. Prediction methods for preventing single-phase reclosing on permanent fault , 1989 .