Abstract Geothermal energy resources are found in many countries. A reasonable and efficient utilization of these resources has been a worldwide concern. The application of geothermal heat pump systems (GHPS) can help increase the efficiency of using geothermal energy and reduce the thermal pollution to the earth surface. However, this is only possible with a proper working fluid. In this paper, a non-azeotropic working fluid (R290/R600a/R123) is presented for a GHPS where geothermal water at 40–45 °C and heating network water at 70–80 °C serve as the low and high temperature heat sources. Experimental results show that the coefficient of performance (COP) of a GHPS using the working fluid is above 3.5 with the condensation temperature above 80 °C and the condensation pressure below 18 bar, while the temperature of the geothermal water is reduced from 40–46 °C to 31–36 °C.