Parameter determination of supplementary subsynchronous damping controller with residue method
暂无分享,去创建一个
This paper adopts residue method to determine the parameters of supplementary subsynchronous damping controller (SSDC) installed in static VAr compensator (SVC). In order to apply residue method, the author deduces a continuous model of SVC adaptable for subsynchronous resonance (SSR) study based on a dynamic phasor method. An example system with SVC based on the IEEE first benchmark model is analyzed. Parameters of SSDC are determined according to the residue associated with the critical torsional mode in the system. Eigenvalue results show that SSDC with parameters set so, can mitigate the occurrence of SSR.
[1] N. Martins,et al. Determination of suitable locations for power system stabilizers and static VAr compensators for damping electromechanical oscillations in large scale power systems , 1989, Conference Papers Power Industry Computer Application Conference.