Ground Fault Current Distribution When a Ground Fault Occurs in HV Substations Located in an Urban Area

The paper presents a method of determination of ground fault current distribution when HV (high voltage) substations are located in urban or suburban areas, or where many relevant data necessary for determination of this distribution are uncertain or completely unknown. The problem appears as a consequence of the fact that many of urban metal installations are situated under the surface of the ground and cannot be visually determined or verifled. On the basis of on-the-site measurements, the developed method enables compensating all deflciencies of the relevant data about metal installations involved with the ∞uctuating magnet fleld appearing around and along a feeding power line during an unbalanced fault. The presented analytical procedure is based on the fact that two measurable quantities, currents in one phase conductor and in one neutral line conductor, cumulatively involve the inductive efiects of all, known and unknown surrounding metal installations. Once, this quantity has been determined, the problem of determination of difierent parts of a ground fault current becomes solvable by using a relatively simple calculation procedure. The presented quantitative analysis indicates at the beneflts that can be obtained by taking into account the presence of surrounding metal installations.

[1]  J. R. Carson Wave propagation in overhead wires with ground return , 1926 .

[2]  F. Provoost,et al.  Measurement of the current distribution near a substation during a single phase to ground fault , 2003 .

[3]  Lj M Popović Testing and evaluating grounding systems for substations located in urban areas , 2011 .

[4]  Alfred Webs,et al.  Short-circuit currents in three-phase systems , 1985 .

[5]  P.S. Dokopoulos,et al.  Homogenous Earth Approximation of Two-Layer Earth Structures: An Equivalent Resistivity Approach , 2007, IEEE Transactions on Power Delivery.

[6]  L. M. Popovic,et al.  Practical method for evaluating ground fault current distribution in station, towers and ground wire , 1998 .

[7]  Janos Endrenyi,et al.  Analysis of Transmission Tower Potentials During Ground Faults , 1967 .

[8]  Ljubivoje M. Popović Comparative analysisof grounding systems formed by MV cable lines with either uninsulated or insulat , 2011 .

[9]  D.P. Labridis,et al.  Earth return path impedances of underground cables for the two-layer earth case , 2005, IEEE Transactions on Power Delivery.

[10]  S. T. Sobral,et al.  Ground potential rise characteristics of urban step-down substations fed by power cables-a practical example , 1988 .

[11]  S. Mangione,et al.  A Simple Method for Evaluating Ground-Fault Current Transfer at the Transition Station of a Combined Overhead-Cable Line , 2008, IEEE Transactions on Power Delivery.

[12]  Ljubivoje M. Popović Transfer characteristics of electric-power lines passing through urban and suburban areas , 2014 .

[13]  Sponsor,et al.  IEEE guide for safety in AC substation grounding , 2013 .

[14]  Ljubivoje M. Popović Improved analytical expressions for the reduction factor of feeding lines consisting of three single‐core cables , 2008 .

[15]  F. Pollaczek,et al.  Uber das Feld einer unendlich langen wechselstromdurchflossen Einfachleitung , 2022 .

[16]  L.M. Popovic Influence of Metal Installations Surrounding the Feeding Cable Line on the Ground Fault Current Distribution in Supplied Substations , 2008, IEEE Transactions on Power Delivery.

[17]  L. M. Popovic,et al.  Efficient reduction of fault current through the grounding grid of substation supplied by cable line , 2000 .

[18]  F. Dawalibi,et al.  Measurements and Computations of Fault Current Distribution on Overhead Transmission Lines , 1984, IEEE Transactions on Power Apparatus and Systems.