Schemes Set for Protecting Parallel Generators with Different Capacity in the Integrated Power System

The output of power stations varies widely with the diverse operating modes in which the vessels integrated power system (IPS) works. Taking two parallel generators with different capacity for example, there are four possible protection schemes set for both the bus breaker and the main breakers of generators. The results show that the setting value used in each of four cases cannot offer appropriate protection for the normal operation of the system. For this reason, a solution is proposed, that is, the time-current principle in combination with the detection of voltage sag. Streszczenie. Przy dwoch polączonych rownolegle generatorach o roznej pojemności trzeba uzywac cztery uklady zabezpieczające dla dwoch lącznikow szynowych i glownych lącznikow generatorow. W artykule zaproponowano nowe rozwiązanie ukladu zabezpieczającego bazujące na analizie czas-prąd i detekcji zapadow napiecia. (Uklady zabezpieczenia generatorow rownoleglych o roznej pojemności dolączonych do zintegrowanego systemu energetycznego)