Lighting retrofit monitoring for the Federal sector-strategies and results at the DOE Forrestal Building
暂无分享,去创建一个
Pacific Northwest Laboratory (PNL), the US Department of Energy (DOE) Federal Energy Management Program (FEMP), and Potomac Electric Power Company (PEPCO) have been conducting short-term monitoring studies at the Forrestal Building, headquarters of the DOE, since 1990. These studies were an integral part of the Shared Energy Savings (SES) lighting retrofit project completed in 1993. The overall goal of the project was to reduce electricity consumption at the Forrestal Building. One objective of the project was to use the building as a model for other federal SES lighting retrofit efforts. A complete short-term monitoring strategy in support of the SES project was developed. The strategy included baseline measurements of electrical consumption, performance measurements of proposed retrofits, and post-retrofit measurements of electricity consumption. Measurements included power consumption, power harmonics, and lighting levels. The results show a 56% reduction in electrical power consumed for lighting, as well as improved power quality and increased lighting levels.