Flashover Performance Test with Lightning Impulse and Simulation Analysis of Different Insulators in a 110 kV Double-Circuit Transmission Tower

The flashover performance of insulators is the foundation of the calculation of precise lightning protection. The material and structure of an insulator affect its flashover performance but the research on the differences in the flashover performance of different insulators and the analysis of the reason for these differences have not been clear. In this paper, lightning impulse flashover tests of two types of insulators (composite and glass insulators) were carried out in the National Engineering Laboratory (Kunming) for Ultrahigh-voltage Engineering Technology. In these tests, the insulators were hung in a 110 kV double-circuit transmission tower and a standard lightning impulse (1.2/50 μs) was applied to the insulators. The discharge path and the 50% impulse flashover voltage of the insulators were recorded. At the same time, the electric fields in the vicinity of different insulators were calculated using the finite element method with COMSOL Multiphysics. The electric field distribution and the uneven coefficient were analyzed. Combined with the flashover test data and the electric field simulation, the relationship between the flashover performance (discharge path and 50% impulse flashover voltage) and the electric field (electric field distribution and uneven coefficient) is found. The simulation results are in accordance with the test data and the conclusions can provide useful references for the external insulation design of transmission lines and the optimization of insulators.

[1]  J. He,et al.  Potential Distribution Analysis of Suspended-Type Metal-Oxide Surge Arresters , 2002, IEEE Power Engineering Review.

[2]  Zhuo Xu,et al.  Influences of Electric-Field Distribution Along the String on the Aging of Composite Insulators , 2013, IEEE Transactions on Power Delivery.

[3]  Qin Hu,et al.  Effects of electric field distribution on icing and flashover performance of 220 kV composite insulators , 2014, IEEE Transactions on Dielectrics and Electrical Insulation.

[4]  S. Rowland,et al.  Electrical and material characterization of field-aged 400 kV silicone rubber composite insulators , 2010, IEEE Transactions on Dielectrics and Electrical Insulation.

[5]  Qin Hu,et al.  Effect of environment factors on ac flashover performance of 3 units of polluted insulator strings under natural fog condition , 2014, IEEE Transactions on Dielectrics and Electrical Insulation.

[6]  M. G. Comber,et al.  Calculation of electric field and potential distribution along nonceramic insulators considering the effects of conductors and transmission towers , 2000 .

[7]  Sarath Kumara,et al.  Simulation of surface charge effect on impulse flashover characteristics of outdoor polymeric insulators , 2010, IEEE Transactions on Dielectrics and Electrical Insulation.

[8]  Xingliang Jiang,et al.  Influence of shed configuration on icing characteristics and flashover performance of 220 kV composite insulators , 2016, IEEE Transactions on Dielectrics and Electrical Insulation.

[9]  Li Li-cheng Lightning Impulse Voltage-time Characteristics of Extra-high Voltage Insulator Strings in High Altitude Area , 2012 .

[10]  Rong Zeng,et al.  Numerical analysis of electric-field distribution around composite insulator and head of transmission tower , 2006 .

[11]  Jinliang He,et al.  Breakdown Process Experiments of 110- to 500-kV Insulator Strings Under Short Tail Lightning Impulse , 2014, IEEE Transactions on Power Delivery.

[12]  P. Gomez,et al.  Optimized design of electric field grading systems in 115 kV non-ceramic insulators , 2013, IEEE Transactions on Dielectrics and Electrical Insulation.

[13]  Jiahong He,et al.  Charge simulation based electric field analysis of composite insulators for HVDC lines , 2014, IEEE Transactions on Dielectrics and Electrical Insulation.

[14]  Masoud Farzaneh,et al.  Flashover Characteristics of Silicone Rubber Sheets under Various Environmental Conditions , 2016 .

[15]  S. Usa,et al.  Electrical field computation of polymeric insulator using reduced dimension modeling , 2015, IEEE Transactions on Dielectrics and Electrical Insulation.

[16]  R. S. Gorur,et al.  Electric potential and field computation along AC HV insulators , 1994 .

[17]  Caixin Sun,et al.  DC Flashover Performance of Various Types of Ice-Covered Insulator Strings under Low Air Pressure , 2012 .

[18]  Bo He,et al.  Influence of flow-electric field on withstand characteristics of HV suspension insulators in sandstorm circumstance , 2016, IEEE Transactions on Dielectrics and Electrical Insulation.

[19]  Hüseyin R. Hiziroglu,et al.  Electromagnetic Field Theory Funda-mentals , 1997 .

[20]  Liu Chao-yi Electric Field Distribution Improvement of Series Connection of Glass Insulator to the High Voltage End of Composite Insulator , 2010 .

[21]  J. Pihler,et al.  Designing a New Post Insulator Using 3-D Electric-Field Analysis , 2009, IEEE Transactions on Power Delivery.