MINLP optimization of mechanical draft counter flow wet-cooling towers

In this paper, the problem of the optimal design of mechanical draft counter flow cooling towers that meets a set of specified constraints is formulated as a mixed-integer nonlinear programming (MINLP) problem. The Merkel's method is used to specify the characteristic dimensions of cooling towers, together with empirical correlations for the loss and overall mass transfer coefficients in the packing region of the tower. Water-to-air mass ratio, water mass flow rate, water inlet and outlet temperatures, operational temperature approach, type of packing, type of draft, height and area of the tower packing, total pressure drop of air flow, power consumption of the fan, and water consumption provide the set of optimization variables. The MINLP problem is formulated so as to minimize the total annual cost of the cooling tower. The performance of the proposed procedure is shown with the solution of six examples.

[1]  James M. Douglas,et al.  Conceptual Design of Chemical Processes , 1988 .

[2]  Mi Sandar Mon,et al.  Heat Exchanger Design , 2008 .

[3]  Aldo R. Vecchietti,et al.  Modeling of discrete/continuous optimization problems: characterization and formulation of disjunctions and their relaxations , 2003, Comput. Chem. Eng..

[4]  Detlev G. Kröger,et al.  Refinement of the Transfer Characteristic Correlation of Wet-Cooling Tower Fills , 2005 .

[5]  F. N Kemmer,et al.  Nalco water handbook , 1979 .

[6]  A. Wexler,et al.  FORMULATIONS FOR THE THERMODYNAMIC PROPERTIES OF THE SATURATED PHASES OF H2O FROM 173.15 TO 473.15 K. , 1983 .

[7]  Detlev G. Kröger,et al.  Loss coefficient correlation for wet-cooling tower fills , 2003 .

[8]  Alan Shivers Foust,et al.  Principles of unit operations , 1960 .

[9]  A. K. M. Mohiuddin,et al.  Knowledge base for the systematic design of wet cooling towers. Part I: Selection and tower characteristics , 1996 .

[10]  Mehmet Sait Söylemez,et al.  ON THE OPTIMUM SIZING OF COOLING TOWERS , 2001 .

[11]  D. G. Kröger,et al.  Air-cooled heat exchangers and cooling towers , 2005 .

[12]  R. L. Webb,et al.  A unified theoretical treatment for thermal analysis of cooling towers, evaporative condensers, and fluid coolers , 1984 .

[13]  Michael Kintner-Meyer,et al.  Cost-optimal analysis of cooling towers , 1994 .

[14]  Michael Kintner-Meyer,et al.  Cost-optimal design for cooling towers , 1995 .

[15]  Refrigerating ASHRAE handbook of fundamentals , 1967 .

[16]  Arturo Jiménez-Gutiérrez,et al.  MINLP synthesis of optimal cooling networks , 2007 .

[17]  Detlev G. Kro¨ger,et al.  Cooling tower performance evaluation: Merkel, Poppe, and e-NTU methods of analysis , 2005 .

[18]  Refrigerating ASHRAE handbook and product directory /published by the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc , 1977 .

[19]  A. F. Mills Basic Heat and Mass Transfer , 1999 .

[20]  I. Grossmann,et al.  A combined penalty function and outer-approximation method for MINLP optimization : applications to distillation column design , 1989 .

[21]  Yousef S.H. Najjar Forced Draft Cooling Tower Performance with Diesel Power Stations , 1988 .

[22]  K. W. Li,et al.  Power Plant System Design , 1985 .

[23]  Mehmet Sait Söylemez,et al.  On the optimum performance of forced draft counter flow cooling towers , 2004 .

[24]  Detlev G. Kröger,et al.  A critical investigation into the heat and mass transfer analysis of counterflow wet-cooling towers , 2005 .