Performance and Availability Analyses of PV Generation Systems in Taiwan

The purpose of this article applies the monthly final energy yield and failure data of 202 PV systems installed in Taiwan to analyze the PV operational performance and system availability. This data is collected by Industrial Technology Research Institute through manual records. Bad data detection and failure data estimation approaches are proposed to guarantee the quality of the received information. The performance ratio value and system availability are then calculated and compared with those of other countries. It is indicated that the average performance ratio of Taiwan’s PV systems is 0.74 and the availability is 95.7%. These results are similar with those of Germany, Switzerland, Italy and Japan. Keywords—availability, performance ratio, PV system, Taiwan

[1]  L. Clavadetscher,et al.  International energy agency PVPS task 2: Analysis of the operational performance of the IEA database PV systems , 2000 .

[2]  D. Collier,et al.  Photovoltaic system reliability , 1997, Conference Record of the Twenty Sixth IEEE Photovoltaic Specialists Conference - 1997.

[3]  K. Otani,et al.  Performance and Reliability of 1 MW Photovoltaic Power Facilities in AIST , 2006, 2006 IEEE 4th World Conference on Photovoltaic Energy Conference.

[4]  Roy Billinton,et al.  Reliability evaluation of engineering systems : concepts and techniques , 1992 .