Effect of grid disturbances on fault-ride-through behaviour of MV-connected DG-units, in especially CHP-plants

In the near future a significant amount of the consumed electrical energy will be generated by distributed generation (DG). Because of the small size these units are normally connected to the local distribution grid [1]. Connection of DG changes the operation of the distribution grid. In order to minimize the effect of DG during grid disturbances some standards oblige immediate disconnection of DG-units. With an increasing number of DG-units this strategy can lead to a disconnection of a large amount of DG-units and jeopardize the security of supply. To prevent large unbalances between generation and load because of disconnection of DG-units some grid operators have defined fault-ride- through requirements. These fault-ride-through requirements are especially applied for large wind parks which are connected to the transmission grid.

[1]  J.M.A. Myrzik,et al.  Grid interaction of MV-connected CHP-plants during disturbances , 2009, 2009 IEEE Power & Energy Society General Meeting.

[2]  Nasser Tleis,et al.  The Development of Grid Code Requirements for New and Renewable Forms of Generation in Great Britain , 2005 .

[3]  J. Machowski Power System Dynamics And Stability , 1997 .

[4]  Math Bollen,et al.  Understanding Power Quality Problems , 1999 .

[5]  Valerijs Knazkins,et al.  Stability of power systems with large amounts of distributed generation , 2004 .

[6]  Z.A. Styczynski,et al.  Dynamic simulation of renewable energy sources and requirements on fault ride through behavior , 2006, 2006 IEEE Power Engineering Society General Meeting.

[7]  Lennart Söder,et al.  Distributed generation : a definition , 2001 .

[8]  Math Bollen,et al.  Different methods for classification of three-phase unbalanced voltage dips due to faults , 2003 .

[9]  I. Erlich,et al.  Grid code requirements concerning connection and operation of wind turbines in Germany , 2005, IEEE Power Engineering Society General Meeting, 2005.

[10]  Jfg Sjef Cobben Power quality : implications at the point of connection , 2007 .

[11]  G. J. Rogers,et al.  Impacts of the distributed utility on transmission system stability , 1996 .

[12]  J.V. Milanovic,et al.  The influence of transformer winding connections on the propagation of voltage sags , 2006, IEEE Transactions on Power Delivery.

[13]  T. Ackermann,et al.  Interaction between distributed generation and the distribution network: operation aspects , 2002, IEEE/PES Transmission and Distribution Conference and Exhibition.

[14]  E. J. Coster,et al.  Comparison of practical fault ride-through capability for MV-connected DG units , 2008 .