A New Kalman Filtering Based Digital Distance Relay

This paper describes the design and test results of a Kalman filtering based digital distance protection scheme. A brief review of voltage and current Kalman filters is followed by sensitivity analysis due to incorrect model parameters. The complete scheme for fault detection, classification, zone computation, and fault location calculation is tested for all types of faults at different locations using simulated data. The major parts of the scheme were tested using the available recorded data. The test results indicated that the proposed scheme has a mean operating time of a quarter of a cycle, insensitive to incorrect model parameters, and represents a low computer burden.

[1]  A.G. Phadke,et al.  Limits to Impedance Relaying , 1979, IEEE Transactions on Power Apparatus and Systems.

[2]  P. Davall,et al.  A Software Design for a Computer Based Impedance Relay for Transmission Line Protection , 1980, IEEE Transactions on Power Apparatus and Systems.

[3]  A. Wright,et al.  Some factors affecting the accuracy of distance-type protective equipment under earth-fault conditions , 1963 .

[4]  Adly Girgis,et al.  Application of Kalman Filtering in Computer Relaying , 1981, IEEE Transactions on Power Apparatus and Systems.

[5]  T. Hlibka,et al.  A digital computer system for EHV substations: Analysis and field tests , 1976, IEEE Transactions on Power Apparatus and Systems.