Survival and growth of micro-organisms on air filtration media during initial loading

A new type of air filtration medium made from a hygroscopic polymer fibre and constructed in three layers was investigated to measure the survival and growth of micro-organisms on this medium in comparison to a widely used fibreglass medium. Both materials were supplied by the manufacturer and tested 'blind'. The materials were loaded in an Airotester unit. Micro-organisms were analysed at 2 weekly intervals for 8 weeks by washing filter samples and plating the solution on to agar media and by vital fluorescence microscopy. Filter samples were also weighed to calculate water content and the pH value of the filter material was measured in the wash out eluate. Vital fluorescence microscopy revealed fungi were able to grow on fibreglass medium, but not on the multi-layered polymer. The colony forming unit (CFU) counts did not increase at a steady rate. There was a significant increase on both materials (P<0.001) during the first 2 weeks which was then followed by a significant decrease in 4 weeks (P<0.001) but the CFU then significantly increased in 6 weeks (P<0.05) which were the highest CFU counts during the 2-month trial. There was a significant difference in CFU counts between the filter materials only in week 2 (P≤0.001) and week 4 (P=0.04). Fewer micro-organisms were extracted from the multi-layered polymer than from the fibreglass medium. Fewer fungal species were identified on the multi-layered polymer (nine species) than on the fibreglass medium (13 species). The pH value on the multi-layered polymer was significantly higher than the fibreglass material but only when clean (P<0.010) and after 2 weeks (P<0.001). A significantly higher water content on the fibreglass medium (P<0.001) also indicated a habitat where a wider range of fungal species and bacteria are able to survive. While there was a reduced survival and growth of micro-organisms on the multi-layered polymer material in the initial month of service life, this advantage was cancelled by the supply of nutrients (particulate matter) that were accumulated on the filter materials after 6 weeks.

[1]  P. Skov,et al.  Aerobiology of schools and public institutions--part of a study. , 1983, Ecology of disease.

[2]  A. Verhoeff,et al.  Health implications of fungi in indoor environments - an overview. , 1994 .

[3]  David A. Sterling,et al.  The effect of air control systems on the indoor distributions of viable particles , 1982 .

[4]  Jan Pejtersen,et al.  Sensory Pollution and Microbial Contamination of Ventilation Filters , 1996 .

[5]  Filter cassette sampling for bacterial and fungal aerosols. , 1994 .

[6]  H. Neumeister,et al.  Nematophagous Fungi – Study by Fluorescence Microscopy and EDX-Technique of the Periodicity of Trap Formation in Soil , 1997 .

[7]  A. Verhoeff,et al.  Biocontamination in air-conditioning. , 1994 .

[8]  Fire Regime and the Abundance of Red Pine , 1993 .

[9]  Robert A. Samson,et al.  Health Implications of Fungi in Indoor Environments , 1994 .

[10]  G. S. Hoog,et al.  A revision of the genus geotrichum and its teleomorphs , 1986 .

[11]  P. Arnow,et al.  Endemic and epidemic aspergillosis associated with in-hospital replication of Aspergillus organisms. , 1991, The Journal of infectious diseases.

[12]  Baarn W. Gams,et al.  Untersuchungen uber die morphologische und biologische Differenzierung in der Fusarium-Sektion Liseola , 1977 .

[13]  Pertti Pasanen,et al.  Hygienic Aspects of Processing Oil Residues in Ventilation Ducts , 1995 .

[14]  A. Verhoeff,et al.  Fungal propagules in house dust. I. , 1994, Allergy.

[15]  W. Gams,et al.  Chloridium and some other dematiaceous hyphomycetes growing on decaying wood , 1976 .

[16]  J. Pitt The genus Penicillium and its teleomorphic states Eupenicillium and Talaromyces , 1981 .

[17]  Antonio Colombi,et al.  Biological Particles in Indoor Environments , 1993 .

[18]  David W. Bearg,et al.  Indoor Air Quality and HVAC Systems , 1993 .

[19]  F. Gyntelberg,et al.  Demonstration of Microorganisms and Dust in Schools and Offices , 1986, Allergy.

[20]  Robert A. Samson,et al.  Introduction to food-borne fungi. , 1989 .