UHF and current pulse measurements of partial discharge activity in mineral oil

Investigations are reported into a range of defects causing partial discharge (PD) activity in high-voltage oil-insulated equipment. The aim is to explore the relationship between radiated ultra-high frequency (UHF) signals and electric charge in a PD current pulse for PD sources in oil insulation. Experiments are performed under high-voltage AC conditions using electrode configurations that included a sharp protrusion, a bad contact, and a free metallic particle. A broadband current transformer is used to measure the PD current pulses with the UHF signals being detected using a pair of sensors mounted inside a metal tank surrounding the PD sources. Current pulses and UHF signals were recorded simultaneously using an oscilloscope with a bandwidth of 3 GHz. The level of correlation between the energy of the radiated UHF signals and the charge content of PD pulses is shown to vary depending on the defect type. Polarity-dependent UHF spectral content and ratio of UHF signal energies measured at the two sensors are shown to exhibit characteristics dependent on the discharge behaviour. These results and the analysis procedures introduced will contribute to the development of effective UHF monitoring systems for oil-insulated high-voltage plant.

[1]  Hitoshi Okubo,et al.  The relationship between partial discharge current pulse waveforms and physical mechanisms , 2002 .

[2]  R. Baumgartner,et al.  Partial discharge. IX. PD in gas-insulated substations-fundamental considerations , 1991, IEEE Electrical Insulation Magazine.

[3]  M.D. Judd,et al.  Partial discharge monitoring of power transformers using UHF sensors. Part I: sensors and signal interpretation , 2005, IEEE Electrical Insulation Magazine.

[4]  B. F. Hampton,et al.  Diagnostic measurements at UHF in gas insulated substations , 1988 .

[5]  P. M. Eleftherion Partial discharge. XXI. Acoustic emission based PD source location in transformers , 1995 .

[6]  Martin D. Judd,et al.  Partial discharge diagnostics for gas insulated substations , 1995 .

[7]  Martin D. Judd,et al.  A pulsed GTEM system for UHF sensor calibration , 1998, IEEE Trans. Instrum. Meas..

[8]  Martin D. Judd,et al.  Applying UHF partial discharge detection to power transformers , 2002 .

[9]  S. Boggs Electromagnetic Techniques for Fault and Partial Discharge Location in Gas-Insulated Cables and Substations , 1982, IEEE Transactions on Power Apparatus and Systems.

[10]  B. F. Hampton,et al.  The excitation of UHF signals by partial discharges in GIS , 1996 .

[11]  Hugh Rudnick California Crisis Influences Further Reforms in Latin America , 2002, IEEE Power Engineering Review.

[12]  Michel Duval,et al.  A review of faults detectable by gas-in-oil analysis in transformers , 2002 .

[13]  M.D. Judd,et al.  Partial discharge monitoring for power transformer using UHF sensors. Part 2: field experience , 2005, IEEE Electrical Insulation Magazine.