The use of ducts to improve the control of supply air temperature rise in UFAD systems: CFD and lab study

Cool supply air flowing through the underfloor plenum is exposed to heat gain from both the concrete slab (conducted from the warm return air on the adjacent floor below the slab) and the raised floor panels (conducted from the warmer room above). The magnitude of this heat gain can be quite high, resulting in undesirable loss of control of the supply air temperature from the plenum into the occupied space. These warmer supply air temperatures can make it more difficult to maintain comfort in the occupied space (without increasing airflow rates), particularly in perimeter zones where cooling loads reach their highest levels. How to predict plenum thermal performance is one of the key design issues facing practicing engineers – evidence from completed projects indicates that excessive temperature rise in the plenum can be a problem.

[1]  F. Bauman Underfloor air distribution (UFAD) design guide , 2003 .

[2]  P. Roache Perspective: A Method for Uniform Reporting of Grid Refinement Studies , 1994 .

[3]  T. Webster,et al.  Underfloor air distribution: thermal stratification , 2002 .

[4]  Zhiqiang John Zhai,et al.  Evaluation of Various Turbulence Models in Predicting Airflow and Turbulence in Enclosed Environments by CFD: Part 2—Comparison with Experimental Data from Literature , 2007 .

[5]  Tom Webster,et al.  Thermal stratification performance of underfloor air distribution (UFAD) systems , 2002 .

[6]  Kwang Ho Lee,et al.  Thermal decay in underfloor air distribution (UFAD) systems: Fundamentals and influence on system performance , 2012 .

[7]  Fred Bauman,et al.  Energy performance of underfloor air distribution systems , 2007 .

[8]  David Faulkner,et al.  Performance of Underfloor Air Distribution in a Field Setting , 2005 .

[9]  Tom Webster,et al.  Testing and modeling of underfloor air supply plenums , 2006 .

[10]  Kwang Ho Lee,et al.  Simplified calculation method for design cooling loads in underfloor air distribution (UFAD) systems , 2011 .

[11]  P. Roache QUANTIFICATION OF UNCERTAINTY IN COMPUTATIONAL FLUID DYNAMICS , 1997 .

[12]  B. Launder,et al.  The numerical computation of turbulent flows , 1990 .

[13]  Tom Webster,et al.  Heat transfer pathways in underfloor air distribution (UFAD) systems , 2006 .

[14]  D N Sørensen,et al.  Quality control of computational fluid dynamics in indoor environments. , 2003, Indoor Air: International Journal of Indoor Environment and Health.

[15]  Fred Bauman Designing and specifying underfloor systems: Shedding light on common myths , 2003 .