Group thermal response testing for energy piles

Thermal response testing is an in situ technique for characterising the thermal conductivity of the ground around a borehole heat exchanger. The test has seen renewed interest in recent years as an increasing number of ground heat exchangers are being constructed to provide renewable heating and cooling energy as part of ground source heat pump systems. The thermal response test involves applying a constant heating power to the ground via a circulating heat transfer fluid. Most test rigs are set up to cater for deep boreholes, with available heat transfer lengths typically more than 100m, and therefore have electrical heater capacities of a corresponding size. Pile heat exchangers are generally much shorter and the heat exchange length can be a little as 10m. This means that many standard thermal response test rigs cannot provide a low enough heating power and there is a risk of excessive temperature changes developing, especially during longer duration tests which can be recommended for larger diameter piles. One solution is to carry out the thermal response test on a group of piles, thereby increasing the effective heated length. This has the added advantage of testing a larger volume of soil. This paper examines the principles behind group thermal response testing for energy piles and considers the advantages and limitations of the approach with reference to a case study