Evaluation of a New Monochloramine Generation System for Controlling Legionella in Building Hot Water Systems

Objective. To evaluate the efficacy of a new monochloramine generation system for control of Legionella in a hospital hot water distribution system Setting. A 495-bed tertiary care hospital in Pittsburgh, Pennsylvania. The hospital has 12 floors covering approximately 78,000 m2. Methods. The hospital hot water system was monitored for a total of 29 months, including a 5-month baseline sampling period prior to installation of the monochloramine system and 24 months of surveillance after system installation (postdisinfection period). Water samples were collected for microbiological analysis (Legionella species, Pseudomonas aeruginosa, Stenotrophomonas maltophilia, Acinetobacter species, nitrifying bacteria, heterotrophic plate count [HPC] bacteria, and nontuberculous mycobacteria). Chemical parameters monitored during the investigation included monochloramine, chlorine (free and total), nitrate, nitrite, total ammonia, copper, silver, lead, and pH. Results. A significant reduction in Legionella distal site positivity was observed between the pre- and postdisinfection periods, with positivity decreasing from an average of 53% (baseline) to an average of 9% after monochloramine application (P > .05). Although geometric mean HPC concentrations decreased by approximately 2 log colony-forming units per milliliter during monochloramine treatment, we did not observe significant changes in other microbial populations. Conclusions. This is the first evaluation in the United States of a commercially available monochloramine system installed on a hospital hot water system for Legionella disinfection, and it demonstrated a significant reduction in Legionella colonization. Significant increases in microbial populations or other negative effects previously associated with monochloramine use in large municipal cold water systems were not observed. Infect Control Hosp Epidemiol 2014;35(11):1356–1363

[1]  M. L. Cristina,et al.  Long-Term Effects of Hospital Water Network Disinfection on Legionella and Other Waterborne Bacteria in an Italian University Hospital , 2014, Infection Control & Hospital Epidemiology.

[2]  M. Dubow,et al.  Susceptibility of Legionella Strains to the Chlorinated Biocide, Monochloramine , 2013, Microbes and environments.

[3]  P. Borella,et al.  Control of Legionella contamination in a hospital water distribution system by monochloramine. , 2012, American journal of infection control.

[4]  P. Bishop,et al.  Effect of free ammonia concentration on monochloramine penetration within a nitrifying biofilm and its effect on activity, viability, and recovery. , 2012, Water research.

[5]  S. Cosgrove,et al.  Electronic-Eye Faucets: Legionella Species Contamination in Healthcare Settings , 2012, Infection Control & Hospital Epidemiology.

[6]  L. Hampton,et al.  Legionellosis—United States, 2000–2009 , 2012, American journal of transplantation : official journal of the American Society of Transplantation and the American Society of Transplant Surgeons.

[7]  V. Yu,et al.  Controlling Legionella in Hospital Drinking Water: An Evidence-Based Review of Disinfection Methods , 2011, Infection Control & Hospital Epidemiology.

[8]  V. Yu,et al.  Environmental culturing for Legionella: can we build a better mouse trap? , 2010, American journal of infection control.

[9]  I. Karagiannis,et al.  Warm, wet weather associated with increased Legionnaires' disease incidence in The Netherlands , 2008, Epidemiology and Infection.

[10]  V. Yu,et al.  Role of Environmental Surveillance in Determining the Risk of Hospital-Acquired Legionellosis: A National Surveillance Study With Clinical Correlations , 2007, Infection Control & Hospital Epidemiology.

[11]  Lisa B. Gelling,et al.  Reducing Legionella Colonization of Water Systems with Monochloramine , 2006, Emerging infectious diseases.

[12]  P Gastmeier,et al.  [Guidelines for preventing health-care-associated pneumonia]. , 2005, Anasthesiologie, Intensivmedizin, Notfallmedizin, Schmerztherapie : AINS.

[13]  Petra Gastmeier,et al.  Should Electronic Faucets Be Recommended in Hospitals? , 2004, Infection Control & Hospital Epidemiology.

[14]  S. Sattar,et al.  Investigation of opportunistic pathogens in municipal drinking water under different supply and treatment regimes. , 2004, Water science and technology : a journal of the International Association on Water Pollution Research.

[15]  Joseph C. Carpenter,et al.  Risk of Hospital-Acquired Legionnaires' Disease in Cities Using Monochloramine Versus Other Water Disinfectants , 2003, Infection Control & Hospital Epidemiology.

[16]  V. Yu,et al.  Experiences of the first 16 hospitals using copper-silver ionization for Legionella control: implications for the evaluation of other disinfection modalities. , 2003, Infection control and hospital epidemiology.

[17]  H Mittermayer,et al.  Non-touch fittings in hospitals: a possible source of Pseudomonas aeruginosa and Legionella spp. , 2001, The Journal of hospital infection.

[18]  Joseph C. Carpenter,et al.  Effect of monochloramine disinfection of municipal drinking water on risk of nosocomial Legionnaires'disease , 1999, The Lancet.

[19]  V. Yu,et al.  Comparison of culture methods for monitoring Legionella species in hospital potable water systems and recommendations for standardization of such methods , 1995, Journal of clinical microbiology.

[20]  Ramon G. Lee,et al.  Factors promoting survival of bacteria in chlorinated water supplies , 1988, Applied and environmental microbiology.

[21]  YU VICTORL. Legionella control by chlorine dioxide in hospital water systems , 2009 .

[22]  Joseph C. Carpenter,et al.  Monochloramine Disinfection of Biofilm-Associated Legionella pneumophila in a Potable Water Model System , 2002 .