잠열 축열식 칠러시스템의 제어 방식에 따른 성능 분석
暂无分享,去创建一个
A chiller, having a thermal storage system, can contribute to load-leveling and can reduce the cost of electricity by using electricity at night. In this study, the control experiments and simulations are conducted using both conventional and advanced methods for the building cooling system. Advanced approaches, such as the `region control method`, divide the control region into five zones according to the size of the building load, and determines the cooling capacities of the chiller and thermal storage. On the other hand, the `dynamic programming method` obtains the optimal cooling capacities of the chiller and thermal storage by selecting the minimum-cost path by carrying out repetitive calculations. The `thermal storage priority method` shows an inferior chiller performance owing to the low-part load operation, whereas the chiller priority method leads to a high electric cost owing to the low utilization of thermal storage and electricity at night. It has been proven that the advanced control methods have advantages over the conventional methods in terms of electricity consumption, as well as cost-effectiveness. According to the simulation results during the winter season, the electric cost when using the dynamic programming method was 6.5% and 8.9% lower than that of the chiller priority and the thermal storage priority methods, respectively. It is therefore concluded that the cost of electricity utilizing the region control method is comparable to that of the dynamic programming method.