Pattern analysis of partial discharges in SF/sub 6/ GIS

The measurement of partial discharge(PD) of several faults in gas-insulated system (GIS) is discussed. Phase-resolved PD patterns have been measured using three different PD detection measuring systems: according to the IEC 270 recommendations, a VHF/UHF measuring system with narrow band filtering, and the UHF measuring system with wide band filtering. PD patterns are compared using computer-based discrimination tools. The influence of the selected center frequency on the PD patterns is discussed for the narrow band VHF/UHF measuring system. The influence of the number and type of GIS components between the discharging defect and the capacitive coupler on the shape of the PD patterns is analyzed. For several GIS components the signal reduction is studied. It was found that the shape of PD patterns is independent on the used PD detection circuit and the propagation path of the PD signals. As a result, discrimination and classification of PD distributions of several studied defects are possible using digital tools.

[1]  B. F. Hampton,et al.  Diagnostic measurements at UHF in gas insulated substations , 1988 .

[2]  B. F. Hampton,et al.  A continuous UHF monitor for gas-insulated substations , 1991 .

[3]  A. Bargigia,et al.  Detection of parallel discharges in gas insulated substations , 1992 .

[4]  E. Gulski,et al.  Computer-aided measurement of partial discharges in HV equipment , 1993 .

[5]  A. Krivda Automated recognition of partial discharges , 1995 .

[6]  Martin D. Judd,et al.  Partial discharge diagnostics for gas insulated substations , 1995 .

[7]  E. Gulski Digital analysis of partial discharges , 1995 .

[8]  E. Gulski,et al.  The use of fractal features for recognition of 3-D discharge patterns , 1995 .

[9]  L. Satish,et al.  Can fractal features be used for recognizing 3-d partial discharge patterns , 1995 .

[10]  W. R. Rutgers,et al.  Acquisition of partial discharges in SF/sub 6/ insulation , 1996, Proceedings of Conference on Electrical Insulation and Dielectric Phenomena - CEIDP '96.

[11]  N. de Kock,et al.  UHF PD detection in gas-insulated switchgear-suitability and sensitivity of the UHF method in comparison with the IEC 270 method , 1996 .

[12]  K. Feser,et al.  Computer aided recognition of defects in GIS , 1996, Conference Record of the 1996 IEEE International Symposium on Electrical Insulation.

[13]  K. Feser,et al.  Sensitivity of the UHF-method for defects in GIS with regard to on-line partial discharge detection , 1996, Conference Record of the 1996 IEEE International Symposium on Electrical Insulation.

[14]  E. Gulski,et al.  Classification of defects in HV components by fractal analysis of PD measurements , 1996, Proceedings of Conference on Electrical Insulation and Dielectric Phenomena - CEIDP '96.

[15]  E. Gulski,et al.  Recognition of PD in SF/sub 6/ insulation using digital data processing , 1996, Proceedings of Conference on Electrical Insulation and Dielectric Phenomena - CEIDP '96.