Experimental investigation on cooling performance of multi-split variable refrigerant flow system with microchannel condenser under part load conditions

Abstract On the basis of a 12.5 kW multi-split variable refrigerant flow (VRF) system, the nominal cooling capacity ratio ( θ ) and the COP of the baseline system with fin-tube heat exchanger (FTHX) and the VRF system with microchannel heat exchanger (MCHX) were obtained for different part load ratios (PLRs). The key control strategies of the VRF system were presented. The charged amount of refrigerant ratio β and the pressure drop Δ P of the MCHXs were also achieved. The experimental results show that the β of the MCHXs was decreased by 26.67–46.67% and the optimum charged amount of refrigerant of a VRF system with an MCHX should obtain a discharge pressure between 3.0 MPa and 3.15 MPa for PLR round 100%. The VRF system with the MCHXs obtained large Δ T HX to avoid refrigerant flashing expansion in long pipe application and it could provide residents with better thermal comfort in hot seasons or regions.

[1]  Reinhard Radermacher,et al.  Experimental Evaluation of the Ventilation Effect on the Performance of a VRV System in Cooling Mode—Part I: Experimental Evaluation , 2008 .

[2]  Junye Shi,et al.  Experimental study on frosting control of mobile air conditioning system with microchannel evaporator , 2011 .

[3]  Xiaohong Hai,et al.  Design and Research of the Digital VRV Multi-Connected Units With Three Pipes Type Heat Recovery System , 2006 .

[4]  Jong Min Choi,et al.  Experimental study on the performance of a simultaneous heating and cooling multi-heat pump with the variation of operation mode , 2009 .

[5]  Liang-Liang Shao,et al.  Comparison of heat pump performance using fin-and-tube and microchannel heat exchangers under frost conditions , 2010 .

[6]  Tolga N. Aynur,et al.  Variable refrigerant flow systems: A review , 2010 .

[7]  S. Chowdhury STUDY OF CONDENSATION OF REFRIGERANTS IN MICRO-CHANNELS FOR DEVELOPMENT OF FUTURE COMPACT MICRO-CHANNEL CONDENSERS , 2008 .

[8]  Yue Ming Li,et al.  Energy simulation and analysis of the heat recovery variable refrigerant flow system in winter , 2010 .

[9]  Yong Chan Kim,et al.  Capacity modulation of an inverter-driven multi-air conditioner using electronic expansion valves , 2003 .

[10]  Reinhard Radermacher,et al.  Field performance measurements of a VRF system with sub-cooler in educational offices for the cooling season , 2012 .

[11]  Predrag Stojan Hrnjak,et al.  Experimental and numerical study on microchannel and round-tube condensers in a R410A residential air-conditioning system , 2008 .