Dynamic Stabilizer Verification Tests at the San Juan Station

The first Torsional Dynamic Stabilizers were installed at the San Juan generating station to control subsynchronous oscillations between the turbine-generator units and the series capacitor compensated transmission system. A description of these devices and their application at this plant is the subject of this paper. A field test program which included control of self-excited torsional oscillations is described. Test results verify that the Dynamic Stabilizers do control San Juan subsynchronous oscillations and allow unrestricted use of the compensation.

[1]  S. Sun,et al.  A Subsynchronous Oscillation Relay - Type SSO , 1981, IEEE Transactions on Power Apparatus and Systems.

[2]  D. G. Ramey,et al.  Theory of the Modulated Reactance Solution for Subsynchronous Resonance , 1982, IEEE Power Engineering Review.

[3]  D.G. Ramey,et al.  Simplified transmission and generation system analysis procedures for subsynchronous resonance problems , 1977, IEEE Transactions on Power Apparatus and Systems.